3 ep2328 - technical data, 4 ep2308-000x, ep2318-000x - process image – BECKHOFF EP2xxx User Manual
Page 24

Product overview
2.6.3
EP2328 Technical Data
Technical data
EP23280001
EP23280002
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
4
M8
M12
Nominal input voltage
24 V
DC
(15%/+20%)
Input filter
3.0 ms
"0" signal voltage
3...+5 V (EN 611312, Type 3)
"1" signal voltage
+11...+30 V (EN 611312, Type 3)
Input current
typically 3 mA (EN 611312, Type 3)
Sensor supply
derived from control voltage, max. 0.5 A total, short
circuit proof
Number of outputs
4
M8
M12
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 2.0 A each channel, total current of all outputs
max. 4.0 A
Short circuit current
max. 4.0 A
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
typically 8 mA per channel
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
4 input bits, 4 output bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)
0°C ... +55°C (according to ATEX, see special
conditions [
Permissible ambient temperature during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus, ATEX
2.6.4
EP2308000x, EP2318000x Process image
DI Inputs
You will find the 4 digital inputs to the module (here using the EP23080001 as an example) under Channel
1 to Channel 4
EP2xxx
24
Version 2.1.0