BECKHOFF EP2xxx User Manual
Page 73

Product overview
8000:01 to 8000:08 DIG Safe state active Ch.1, Output 1 to Output 8 (default: TRUE)
Specifies whether or not the outputs should adopt a safe state in the case of network failure.
Value
Meaning
FALSE
Safe state disabled
TRUE
Safe state enabled
8001:01 to 8001:08 DIG Safe state value Ch.1, Output 1 to Output 8 (default:
FALSE)
Specifies what the safe state is.
Value
Meaning
FALSE
Output switched off
TRUE
Output switched on
Definitions for the behavior of the outputs in the presence of a shortcircuit
F800:0 DO Settings (Safe State Value)
Table 4: F800:01 Disable shut off (default: FALSE)
Value
Meaning
FALSE
If a shortcircuit occurs at one output, all outputs of
the module will be switched off.
This disabling can be removed through the process
data value Reset Outputs.
TRUE
If a shortcircuit occurs at one output, only this output
of the module will be switched off.
After the short circuit has been eliminated, this output
is automatically enabled again. see "Extracted nested
table 9"