2 ep2308, ep2318 - technical data – BECKHOFF EP2xxx User Manual
Page 23

Product overview
2.6.2
EP2308, EP2318 Technical Data
Technical data
EP23080001
EP23080002
EP23180001
EP23180002
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
4
M8
M12
M8
M12
Nominal input voltage
24 V
DC
(15%/+20%)
Input filter
3.0 ms
3.0 ms
10 µs
10 µs
"0" signal voltage
3...+5 V (EN 611312, Type 3)
"1" signal voltage
+11...+30 V (EN 611312, Type 3)
Input current
typically 3 mA (EN 611312, Type 3)
Sensor supply
derived from control voltage, max. 0.5 A total, shortcircuit proof
Number of outputs
4
M8
M12
M8
M12
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 0.5 A each channel
Short circuit current
max. 1.5 A
Module electronic supply
derived from control voltage Us
Module electronic current
consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
typically 8 mA per channel
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
4 input bits, 4 output bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature
during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)
0°C ... +55°C (according to ATEX, see special conditions [
Permissible ambient temperature
during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus, ATEX
EP2xxx
23