2 ep2816-0008 - technical data, 3 ep2816-0008 - status-leds – BECKHOFF EP2xxx User Manual
Page 52

Product overview
2.12.2
EP28160008 Technical Data
Technical data
EP28160008
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of outputs
16
25 pin SUBD socket
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 0.5 A each channel, individually shortcircuit proof, total
current of all outputs max. 4 A
Short circuit current
max. 1.5 A
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
max. 30 mA for all channels
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
16 output bits, 16 input bits (diagnostic)
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature during
operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)
Permissible ambient temperature during
storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.12.3
EP28160008 StatusLEDs
Fig. 36: EP28160008 StatusLEDs
EP2xxx
52
Version 2.1.0