BECKHOFF EP2xxx User Manual
Page 165

Comissioning/Configuration
Index
Name
Meaning
Data type
Flags
Default
8011:0
DIG Safe state
value
UINT8
RO
0x08 (8
dec
)
8011:01
Output 9
0
bin
DIG Safe state
value for
output 9 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 9 = 1
8011:02
Output 10
0
bin
DIG Safe state
value for
output 10 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 10 = 1
8011:03
Output 11
0
bin
DIG Safe state
value for
output 11 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 11 = 1
8011:04
Output 12
0
bin
DIG Safe state
value for
output 12 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 12 = 1
8011:05
Output 13
0
bin
DIG Safe state
value for
output 13 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 13 = 1
8011:06
Output 14
0
bin
DIG Safe state
value for
output 14 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 14 = 1
8011:07
Output 15
0
bin
DIG Safe state
value for
output 15 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 15 = 1
8011:08
Output 16
0
bin
DIG Safe state
value for
output 16 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 16 = 1
Index 8020 DIG Safe state active Ch.3
The outputs the bit DIG Safe state active is set for, are switched to the value that is specified in Safe state
value, in case of status Operational (OP) is left.
Status Operational (OP) is left if communication to the master is interrupted, for example at power
breakdown at the master or cable breakage.
EP2xxx
165
Version 2.1.0