Index f000 modular device profile, Index f008 code word, Index f010 module list – BECKHOFF EP2xxx User Manual
Page 189: Index f600 dig inputs, Index f700 dig outputs

Comissioning/Configuration
Index F000 Modular device profile
Index
Name
Meaning
Data type
Flags
Default
F000:0
Modular device
profile
general
information
about the
Modular Device
Profile
UINT8
RO
0x02 (2
dec
)
F000:01
Module index
distance
Index distance
between the
objects of two
channels
UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum
number of
modules
number of
channels
UINT16
RO
0x0003 (3
dec
)
Index F008 Code word
Index
Name
Meaning
Data type
Flags
Default
F008:0
Code word
UINT32
RW
0x00000000
(0
dec
)
Index F010 Module list
Index
Name
Meaning
Data type
Flags
Default
F010:0
Module list
UINT8
RW
0x03 (3
dec
)
F010:01
SubIndex 001
UINT32
RW
0x00000118
(280
dec
)
F010:02
SubIndex 002
UINT32
RW
0x00000118
(280
dec
)
F010:03
SubIndex 003
UINT32
RW
0x00000118
(280
dec
)
Index F600 DIG Inputs
Index
Name
Meaning
Data type
Flags
Default
F600:0
DIG Inputs
UINT8
RO
0x10 (16
dec
)
F600:01
Safe state active
BOOLEAN
RO
0x00 (0
dec
)
F600:02
Error channel 1
BOOLEAN
RO
0x00 (0
dec
)
F600:03
Error channel 2
BOOLEAN
RO
0x00 (0
dec
)
F600:04
Error channel 3
BOOLEAN
RO
0x00 (0
dec
)
F600:05
Us Undervoltage
BOOLEAN
RO
0x00 (0
dec
)
F600:06
Up Undervoltage
BOOLEAN
RO
0x00 (0
dec
)
F600:0E
Sync error
BOOLEAN
RO
0x00 (0
dec
)
F600:10
TxPDO Toggle
BOOLEAN
RO
0x00 (0
dec
)
Index F700 DIG Outputs
Index
Name
Meaning
Data type
Flags
Default
F700:0
DIG Outputs
UINT8
RO
0x02 (2
dec
)
F700:01
Set safe state
BOOLEAN
RO
0x00 (0
dec
)
F700:02
Reset outputs
BOOLEAN
RO
0x00 (0
dec
)
EP2xxx
189
Version 2.1.0