EP2316000x Technical Data
Technical data
EP23160003
EP23160008
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
8
Input connections
25 pin SUB‐D socket ﴾pins 1 ‐
8﴿ [
Nominal input voltage
24 V
DC
(15%/+20%)
Input filter
10 µs
"0" signal voltage
3...+5 V (EN 611312, Type 3)
"1" signal voltage
+11...+30 V (EN 611312, Type 3)
Input current
typically 3 mA (EN 611312, Type 3)
Sensor supply
derived from control voltage, max. 0.5 A total, shortcircuit
proof
Number of outputs
8
Output connections
25 pin SUB‐D socket ﴾pins 9 ‐
18﴿ [
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 0.5 A each channel, individually shortcircuit proof, total
current of all outputs max. 4 A
Short circuit current
max. 1.5 A
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
max. 30 mA for all channels
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
Process
data
8 input bits, 8 output bits
Diagnostic 8 diagnostic input bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature during
operation
25°C ... +60°C
25°C ... +60°C
0°C ... +55°C (according to
cULus, see UL Requirements)
Permissible ambient temperature during
storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP20
IP65, IP66, IP67 (conforms to
EN 60529)
Installation position
variable
Approvals
CE
CE, cULus
EP2xxx
28