2 ep2008 - technical data, 3 ep2008-000x - process image – BECKHOFF EP2xxx User Manual
Page 14

Product overview
2.3.2
EP2008 Technical data
Technical data
EP20080001
EP20080002
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of outputs
8
M8
M12
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 0.5 A each channel
Short circuit current
typically 1.5 A
Module electronic supply
derived from control voltage Us
Module electronic current
consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
typically 8 mA per channel
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
8 output bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature
during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)
0°C ... +55°C (according to ATEX, see special conditions [
92])
Permissible ambient temperature
during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227, EN 60068229
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus, ATEX
2.3.3
EP2008000x Process image
Channel 1 to Channel 8
You will find the 8 digital outputs from the module (here using the EP20080001 as an example) under
Channel 1 to Channel 8.
EP2xxx
14
Version 2.1.0