BECKHOFF EP2xxx User Manual
Page 138

Comissioning/Configuration
Index
Name
Meaning
Data type
Flags
Default
8001:0
DIG Safe state
value
UINT8
RO
0x08 (8
dec
)
8001:01
Output 1
0
bin
DIG Safe state
value for
output 1 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 1 = 1
8001:02
Output 2
0
bin
DIG Safe state
value for
output 2 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 2 = 1
8001:03
Output 3
0
bin
DIG Safe state
value for
output 3 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 3 = 1
8001:04
Output 4
0
bin
DIG Safe state
value for
output 4 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 4 = 1
8001:05
Output 5
0
bin
DIG Safe state
value for
output 5 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 5 = 1
8001:06
Output 6
0
bin
DIG Safe state
value for
output 6 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 6 = 1
8001:07
Output 7
0
bin
DIG Safe state
value for
output 7 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 7 = 1
8001:08
Output 8
0
bin
DIG Safe state
value for
output 8 = 0
BOOLEAN
RW
0
bin
1
bin
DIG Safe state
value for
output 8 = 1
Index 8010 DIG Safe state active Ch.2
The outputs the bit DIG Safe state active is set for, are switched to the value that is specified in Safe state
value, in case of status Operational (OP) is left.
Status Operational (OP) is left if communication to the master is interrupted, for example at power
breakdown at the master or cable breakage.
EP2xxx
138