Lx / Ls Series

32

2.7.2 EHV Option Ls Series -Supplemental Specifications

Specifications for Ls units with -EHV voltage range option installed are same the Lx with

–EHV

option. See paragraph 2.6.2.

2.7.3 -HF Option Supplemental Specifications

Specification for Ls units with -HF frequency range option installed are same as standard Ls unit
except where noted below.

Frequency Range

Model

3000Ls-HF, 4500Ls-HF

, 6000Ls-HF

9000Ls/2-HF, 13500Ls/3-HF

12000Ls/3-HF, 18000Ls/3-HF

Three phase mode

45 Hz - 5000 Hz

45 Hz - 2000 Hz

Single phase mode

45 Hz - 5000 Hz

45 Hz - 2000 Hz

Output

Programming
Accuracy:

< 1000 Hz

± (0.05% + 0.25 V) from 5V to FS.

> 1000 Hz

± (0.1% + 0.1% / KHz + 0.3V) from 5V to FS

Output Noise:
(20 kHz to 1 MHz)

< 250 mV

RMS typical

For output frequencies up to 1000 Hz, refer to standard measurement specifications. For output
frequencies above 1000 Hz, see table below.

Parameter

Range

Accuracy ( )

Resolution

1 Phase Mode

3 Phase Mode

Frequency

1

45.00 - 5000.0 Hz

0.1% ± 1 digit

0.01 Hz to 81.91 Hz
0.1 Hz to 819.1 Hz
1 Hz > 819.1 Hz

Phase

45.00 - 100.0 Hz
100.0 - 2000 Hz
> 2000 Hz

0.5°


0. 1°

RMS Voltage

0 - 400 Volts
< 1000 Hz
> 1000 Hz

0.05% + 0.25V

0.1% + 0.1% / KHz + 0.3V

0.01 Volt

RMS Current

0 - 50 Amps

0.5% + 0.15A

0.5% + 0.05A

0.001 Amp

Peak Current

0 - 150 Amps

0.5% + 0. 5A

0.5% + 0.15A

0.001 Amp

Crest Factor

1.00

– 10.00

1.5 %

1.5 %

0.01

VA Power

0 - 6 KVA

0.5% + 9 VA

0.5% + 3 VA

1 VA

Real Power

0 - 6 KW

0.5% + 9 W

0.5% + 3 W

1 W

Power Factor

0.00 - 1.00

0.03

0.01

0.01

1

Frequency measurement specifications valid with output voltage of 30Vrms or higher. If output relay is open,

frequency measurement will return 0.0 Hz.