Lx / Ls Series

184

SXF 401 Tests

– Revision F

SXF401

Emergency SS Limits Volt and Freq. Rev F

Condition

Duration (s)

Nominal Voltage

A

Vnom=115V, Fnom=60 Hz - Nominal

1800

B

Vnom=115V, Flow=59.5 Hz - Nominal

1800

C

Vnom=115V, Fhigh=60.5 Hz - Nominal

Low Voltage

D

Vlow =105V, Fnom=60 Hz - Low

1800

E

Vlow=105V, Flow= 59.5 Hz- Low

1800

F

Vlow=105V, Fhigh=60.5 Hz - Low

1800

High Voltage

G

Vhigh=125V, Fnom=60 Hz - High

1800

H

Vhigh=125V, Flow=59.5 Hz- High

1800

I

Vhigh=125V, Fhigh=60.5 Hz - High

1800

SXF 501 Tests

Starting operations are not applicable to AC Utilization Equipment.

SXF 601 Tests

– Revision F

SXF601

Power Failure - One Phase

Condition

Duration (s)

A

100 msec

52

B

500 msec

54

C

2 sec

66

SXF 602 Tests

– Revision F

Not applicable for single-

phase EUT’s.

SXF 603 Tests

– Revision F

SXF603

Power Failure

– Phase Reversal

Condition

Duration (s)

N/A

Use physical L-N connection reversal
Apply Vnom = 115 V, Fnom = 60 Hz