User Manual

Lx / Ls Series

13

2.1.2 Output

Output Parameter

Specification

Modes

AC

Voltage:

Ranges (L-N):

Lx Series

Ls Series

Low range

0 - 150 Vrms

0 - 135 Vrms

High range

0 - 300 Vrms

0 - 270 Vrms

Resolution:

0.1 V

0.1 V

Programming
Accuracy:

± (0.05% + 0.25 V) from 5V to FS.

Distortion THD

1

:

Standard:
< 1 %

[45 - 1000 Hz]

< 1 % + 1%/kHz

[> 1000 Hz]

(harmonics and noise to 300 kHz)

With

–HF and –LKM option:

< 2 %

[45 - 1000 Hz]

< 2 % + 1%/kHz

[> 1000 Hz]

(harmonics and noise to 300 kHz)

Load Regulation:
ALC mode ON

0.1 % FS

External Sense

Up to 10Vrms can be dropped across each load lead Fout < 400 Hz.

Up 2.5 Vrms can be dropped across each load lead Fout > 400 Hz

Internal or External sense selectable.

Line Regulation:

0.02% for 10% input line change

DC Offset Voltage:

0.0 V

Output Noise:
(20 kHz to 1 MHz)

< 100 mV

RMS typical

Output Coupling

Transformer coupled

Output Impedance
(Z)

Z = Vrange * 0.001 / I_load

Power

– Lx Series (total power for all phases, either range, at full scale voltage)

35° C Ambient

50° C Ambient

Model

3000Lx

4500Lx

6000Lx

3000Lx

4500Lx

6000Lx

Single Phase Mode

3 KVA

4.5 KVA

5.76 KVA

3 KVA

4 KVA

5 KVA

Three Phase Mode (per

phase)

1 KVA

1.5 KVA

1.9 KVA

1 KVA

1.35 KVA

1.7 KVA

Model

9000Lx/2

12000Lx/2

9000Lx/2

12000Lx/2

Single Phase Mode

9 KVA

11.5 KVA

8 KVA

10 KVA

Three Phase Mode (per

phase)

3 KVA

3.8 KVA

2.7 KVA

3.3 KVA

Model

13500Lx/3

18000Lx/3

13500Lx/3

18000Lx/3

1

The distortion specification for the Lx Series applies at full-scale voltage, full resistive load conditions.