AM Series Boilers and Water Heaters

CHAPTER 5 – OPERATION

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 99 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

5.1.1 Control Panel Display - Boilers

During normal operation, the display remains off, except if the unit goes into Lockout, or has A
Blocking error. Pressing any button will activate the display, which will stay on for 30 minutes
from the time of the last button press.

5.1.2 Startup Procedure - Boilers

This section applies only to AM Series boilers. For Water Heaters, refer to the next section 5.1.

Boiler Startup Procedure

1. Open the manual gas shutoff valve.

2. Switch ON electric power to the boiler.

3. If the display shows code Err 65, it means that the polarity has not been observed between

phase and neutral (Call service department to restore the situation, do not attempt to repair
it).

4. Press button

or

to setup the heating temperature desired, then press RESET

key to save the change.

5. Press button

and

to setup the domestic hot water temperature desired, then

press RESET key to save the change.

The flame control will start-up the burner. If the burner fails to ignite within 60 seconds, the
boiler will automatically attempt ignition another four times, after which if it fails to start-up, it will

shut down and the display will show Loc 01 together with icon

.

If the boiler goes into any lockout or blocking error, the display will show icon

and the

corresponding burner icon (

or

) will blink.

To restore the normal operating condition, press RESET key one time and the display will show
the type of lockout. Press the RESET key again. To return to normal display mode, press and
hold the RESET button for at least 5 seconds.

The boiler will automatically attempt another start-up.

Now the boiler will continue to operate in relation to the service requested and will show:

The icon

if the heating service is enabled.

Blinking

if heating service is active (boiler is warming the heating plant).

The icon

if a domestic hot water service is enabled;

Blinking

if a domestic hot water service is active (and boiler is loading an indirect water

heater);