AM Series Boilers and Water Heaters

CHAPTER 3 – INSTALLATION

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 37 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

Flow Switch/LWCO: A flow switch comes with every unit and must be field installed. For

more information about the flow switch or optional LWCO, see Section 3.11.7.

Indirect water heaters: Feld supplied. This boiler may be piped to an indirect water heater

to heat domestic hot water with the space heat transfer medium. The indirect water heater is
connected to the system supply piping. A pump controlled by the boiler’s control will regulate

the flow of water through the indirect water heater. The indirect water heater’s temperature
will be regulated by the boiler’s control. The boiler is pre-

configured to control the operation

of the DHW pump with Domestic Hot Water Prioritization programming.

CAUTION!

It is up to the installer to ensure that the minimum

system flow is

met, otherwise the flow sensors automatically stop the burner.

WARNING!

The National Standard Plumbing Code, the National Plumbing
Code of Canada and the Uniform Plumbing Code limit the

pressure of the heat transfer fluid to less than the minimum
working pressure of the potable water system up to 30 psi

maximum. Also, the heat transfer fluid must be water or other non-

toxic fluid having a toxicity of Class 1, as listed in Clinical
Toxicology of Commercial Products, 5th Edition.

Filter:

Field supplied. A filter or equivalent multipurpose strainer is recommended at the

return pipe of the boiler to remove system particles from older hydronic systems and protect
newer systems.