beautypg.com

Am series boilers and water heaters – AERCO AM Series Boiler User Manual User Manual

Page 127

background image

AM Series Boilers and Water Heaters

CHAPTER 8 – SPARE PARTS

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 127 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

Condensate System Inspection and Maintenance (Cont.)

8. Replace the condensate cover and reinsert the condensate collection box assembly back

into the unit.

WARNING!

The condensate collection box must be filled with water to prevent

flue gas emissions from escaping during unit operation. Failure to
comply with this requirement can result in dangerous levels of
carbon monoxide.

9. Open the manual gas shutoff valve.

10. Restore electrical power to the unit and return to service.

WARNING!

The condensate neutralizer box MUST be installed correctly into
the unit, as shown in Figures 2-3, 2-4, 2-5, and 2-6. If you do not
install the condensate collection box into its correct position, it will
result in combustion gases will entering the room and creating a
dangerous condition.