4.4 Boiler Startup Procedure

This section applies only to AM Series boilers. Refer to the next section for starting an AM
Series water heater. To start the boiler, do the following:

Boiler Startup Procedure

1. Open the manual gas shut off valve (Figure 3-37),

2. Turn the unit power switch to ON (item “T” in Figure 4-1).

NOTE

The thermostat is adjusted to its lowest temperature position when
shipped from the factory.

3.

The boiler will fire only when there is a call for heat and the heating temperature setting is
higher than the actual supply temperature. Hold buttons

or

to select the desired

heating temperature. If the external temperature sensor is connected (See Section 3.14.5),
check that the calculated temperature (See user Menu, Section 5.3, parameter 1012 or
parameter 1107) is higher than the actual boiler temperature and that the outdoor
temperature (See user Menu, Section 5.3, parameter 1004) is lower than “warm weather
shut down temperature”, (See Section 5.4, parameter 2020 in Installer Menu).

4. If the boiler is connected to an indirect water heater (See Section 3.11.12),

press buttons

and

to select the desired domestic hot water temperature.

4.5 Water Heater Startup Procedure

This section applies only to AM Series water heaters. Refer to the previous section for starting
an AM Series boiler. To start the water heater, do the following:

Water Heater Startup Procedure

1. Open the manual gas shut off valve (Figure 3-40),

2. Turn the unit power switch to ON (item “T” in Figure 4-1).

NOTE

The thermostat is adjusted to its lowest temperature position when
shipped from the factory.

3. The unit will fire only when the domestic hot water setting is higher than the storage tank

temperature (parameter 1002). Press buttons

or

to select the desired

storage tank temperature.

4. If the display gives a Low water flow error (see Section 5.7), repeat the air purging

operations.