Am series boilers and water heaters – AERCO AM Series Boiler User Manual User Manual
Page 81
![background image](/manuals/659332/81/background.png)
AM Series Boilers and Water Heaters
CHAPTER 3 – INSTALLATION
OMM-0100_0B
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 81 of 156
GF-146
Ph.: 800-526-0288
PRI - 07/14/14
Connecting the Gas Supply to the Unit (Cont.)
4. Purge all air from the gas supply piping.
5. Before placing the appliance in operation, check the appliance and its gas connection for
leaks.
a) The appliance must be disconnected from the gas supply piping system during any
pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5 kPa).
b) The appliance must be isolated from the gas supply piping system by closing a manual
shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 PSIG (3.5 kPa).
c) The appliance and its gas connection must be leak tested before placing it in operation.
6. Use pipe sealing compound compatible with propane gas. Apply sparingly only to male
threads of the pipe joints so that pipe dope does not block gas flow.
WARNING!
• Do not attempt to support the weight of the piping with the
water heater or its accessories.
• Never use an open flame to test for gas leaks. Always use an
approved leak detection method.
• Failure to apply pipe sealing compound can result in severe
personal injury, death, or substantial property damage.
The unit is shipped ready to fire on natural gas. Check appliance rating plate to determine which
fuel the appliance is set for. If set to natural gas, it may be converted to propane gas following
instructions in Section 3.17.6.