CHAPTER 3 – INSTALLATION

Page 78 of 156

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0100_0B

PRI - 07/14/14

Ph.: 800-526-0288

GF-146

3.16.5.21 Installing Multiple Vent and Air Vertical Terminations

Install multiple vent and air terminations in a roof as follows:

Installing Vertical Multiple Vent and Air Roof Terminations

1. When terminating multiple units, terminate each vent/air connection as shown in Figure 3-

38.

2. Place roof penetrations to obtain minimum clearance of 12 inches between edge of air

intake elbow and adjacent vent pipe of another appliance for U.S. installations

3. The air inlet is part of a direct vent connection. It is not classified as a forced air intake with

regard to spacing from adjacent appliance vents.

Figure 3-38: Installing Multiple Vent and Air Vertical Terminations – Two