beautypg.com

8 minimum water flow, 9 heating system pressure test, Am series boilers and water heaters – AERCO AM Series Boiler User Manual User Manual

Page 97

background image

AM Series Boilers and Water Heaters

CHAPTER 4 – UNIT START-UP

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 97 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

Combustion Calibration (Cont.)

18. Turn ON the main power to the unit.

19. Repeat Step 3 through Step 10 again.

20. Turn OFF the main power to the unit.

21. Disconnect plug “B” from connector “D” and connect it to connector “E” of the “Burner 4”, if

present (See Figure 4-3).

22. Turn ON the main power to the unit.

23. Repeat Step 3 through Step 10 again.

24. Turn OFF the main power to the unit.

25. Close the combustion analysis probe “H” in Figure 3-25 with a suitable cap in accordance

with the vent pipe manufacturers’ instructions.

WARNING!

Once the cap “L” in Figure 3-28 is correctly installed with the unit
at high fire, check that there are no leaks and that the cap is
mechanically secure.

4.8 Minimum Water Flow

This unit is self-protected against low water flow. A water flow meter (Boiler: item “16”, Figure
2-1 or Water Heater: item “18”, Figure 2-7) continuously monitors the water flow to each burner.
If the water flow decreases below the minimum stated, the burner automatically shuts off.

This value is adjustable via parameter 3035.

4.9 Heating System Pressure Test

If the pressure inside the heating circuit falls below the minimum pressure for the system, the
appliance switches off and the display “N” as per Figure 4-1, shows Err 59 to indicate that it is
necessary to restore t

he correct pressure. Open the filling valve and check the pressure on the

pressure gauge “M” of Figure 4-1, the word Err 59 will disappear when the pressure is back at
the right value. To prevent acci

dental relief valve openings, fill the heating circuit slowly.

This value is adjustable via parameter 3022.

CAUTION!

During normal operations, the filling valve must always remain in
the closed position.

If after one month the pressure cont

inues to decrease, call a qualified service technician.

CAUTION!

Continual fresh make-up water will reduce boiler life. Mineral
buildup in the heat exchanger reduces heat transfer, overheats
the stainless steel heat exchanger, and causes failure. Addition of
oxygen carried in by makeup water can cause internal corrosion in
system components. Leaks in boiler or piping must be repaired at
once to prevent makeup water entering the boiler.