5.1.3 Boiler Summer Mode

To disable the heating functions for a prolonged period, leaving only the domestic hot water

function, press the

key until the word OFF is displayed. Then press RESET button to

save the change. Now the heating service is disabled, and is indicated by the

icon

disappearing from the display.

5.1.4 Boiler Winter Mode

In Winter mode, by means of the pumps, the boiler sends the water to the system at the

temperature set using key

and

of Figure 5-1.

When the temperature inside the boiler reaches the temperature setpoint, the burner starts to

modulate the flame so as to reduce the output to a minimum. If the temperature rises further,
the burner shuts down. Simultaneously, the pump which sends the water to the system is

switched on and off by the room thermostat. This can be observed by indicator

of Figure 5-

1 blinking or not in correspondence with the on and off cycle of the pump.

CAUTION!

Because the boiler freeze protection function depends upon the
electrical and gas supply, it is mandatory to install a safety device
that alarms the user in case the unit room reaches a temperature
near 50°F (10°C).

5.1.5 Adjusting the Domestic Hot Water Temperature - Boilers

The domestic hot water temperature is adjusted by pressing buttons

and

.

When the buttons are pressed, the display, item “N” in Figure 5-1, shows the domestic hot water
setpoint being selected. The range within which the domestic hot water can be set is 104°F
(40°C) to 140°F (60°C).