beautypg.com

Am series boilers and water heaters – AERCO AM Series Boiler User Manual User Manual

Page 124

background image

AM Series Boilers and Water Heaters

CHAPTER 8 – SPARE PARTS

Page 124 of 156

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0100_0B

PRI - 07/14/14

Ph.: 800-526-0288

GF-146

6.1.17 Ignition and Flame Detection Sensor Electrode Positioning

For the heater to work properly the electrodes must be positioned as listed below and shown in
Figure 6-7:

Ignition and Flame Detection Electrode Positioning

To insure correct functioning of the burner, the distances listed below should be carefully

verified by hand using calipers.

• The distance between the ignition electrodes “A” and “B”, must be between 0.08 in (2

mm), and 0.10 in (2.5 mm);

• The distance of the ignition electrodes to the burner surface must be between 0.20 in

(5.0 mm), and 0.22 in (5.5 mm);

• The dist

ance of the flame detection electrode to the burner surface must be between

0.23 in (6.0 mm), and 0.27 in (7.0 mm).

Figure 6-7: Positioning the Ignition & Flame Detection Sensor Electrodes