3.14.1.1 Connecting Units in Cascade (Boilers or Water Heaters)

To connect the heater in cascade you have to follow the electrical connections as per Figure 3-
24. A maximum of eight heaters can be connected in a cascade (Figure 3-24 shows a
connection of four heaters).

After the electrical power connection is made, activate the BUS communication to the HC
command by performing the following:

Activating the Cascade BUS Communication

1. Access to unit interior (see Section 6.1.15).

2. Move the S4 selector switch of the Burner 1 (Master) board to the OFF position. See Figure

6-12 to identify the S4 selector switch of the Burner 1 (Master) board.

3. Move the S4 selector switch of the MODBUS interface (item 13 in Figures 2-3 and 2-6), to

the ON position.

The HC Command (cascade manager) is supplied on demand. For additional information
concerning water, gas, flue exhaust, and air intake connections, contact AERCO technical
support.