4 installer menu – boilers and water heaters, Am series boilers and water heaters – AERCO AM Series Boiler User Manual User Manual
Page 108
![background image](/manuals/659332/108/background.png)
AM Series Boilers and Water Heaters
CHAPTER 5 – OPERATION
Page 108 of 156
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0100_0B
PRI - 07/14/14
Ph.: 800-526-0288
GF-146
5.4 Installer Menu – Boilers and Water Heaters
This menu of parameters is
available to qualified technicians for the purpose of analyzing the
function of, and making adjustments to, the unit.
Parameters for “Burner 1” are applicable for that burner only. If you want to see the same
parameters for the other burners you must connect the display to the burner you want to see per
the instruction in Section 6.1.2.
To enter and make changes in the Installer Menu, perform the following steps:
Installer Menu Navigation and Adjustment
1. To enter the Installer Menu, press and simultaneously hold down both the
RESET
and
buttons or 5 seconds until the icon is displayed.
, then release the buttons.
After entering the Installer Menu, the 2000 series of parameters, as shown in Figure 5-5, are
available for display and editing.
2. To scroll through the list of parameters, press buttons
and
.
3. Once the desired parameter is displayed, it can be selected for editing by pressing the
RESET
button once (the displayed value will start blinking) and then using the
and
buttons to change the value, up or down.
4. To confirm the new value, press and release the
RESET
button before moving to the next
parameter.
5. To exit the Installer Menu, press and hold RESET button for more than 5 seconds until the
icon is no longer shown in the display.