KMC Controls STE-1422 User Manual

KMC Controls Sensors

background image

STE-1421/1422

1

Installation Guide

Installation Guide

Contents

Mounting and Wiring

1

Accessories 2
Specifications 2
Maintenance 2
Configuration 2
More Information 2
Important Notices 2

Mounting and Wiring

Immersion probes measure the temperature inside

pipes carrying liquid or steam and are installed in a

304 stainless-steel thermowell. Mount the thermow-

ell horizontally or with the open end facing down

(to allow any condensation to drain). Position the

thermowell to prevent contact with the inside of the

pipe.

1. Install the pipe fittings required, by local code,

for a thermowell into the dry/drained pipe. If the

system is pressured, use a hot tap.

2. Install the thermowell. (See the Accessories

section.)

3. Fill the well with thermal compound to ensure

complete conductivity from well to probe.

NOTE: The probe can slide within its collar on the

case as it is inserted into the thermowell.

4. Remove the screws holding the cover to the case

and remove the cover.

5. Insert the probe into the well and tighten the

threaded connection on the case.

6. From inside the case, push the probe as far as it

will go into the well.

7. Feed the thermistor wire leads through the

conduit or hole opening.

8. Connect the thermistor wires to the cable with

butt-splices or soldering. (Wire nuts are not

recommended.) The two-wire sensor is not

polarity sensitive.

9. Reinstall the cover and screws.

Thermowells Installed

ABS Enclosure

Metal Enclosure

4.56"

115.8 mm

3.320"

84.3 mm

Various Probe

Lengths

Ø 0.850"

0.25"

6.35 mm

304 Series S/S Probe

1/2" NPT

4.24 “

107.7 mm

Various Probe Lengths

8X Ø 0.875”

2.04

51.8 mm

4.0 “

101.6 mm

0.25 “

6.35 mm

304 Series S/S Probe

1/2” NPT

2.10 “

53.3 mm

0.875 “

22.2 mm

2.110"

53.6 mm

0.875"

22.2 mm

Temperature Sensor, Immersion

STE-1421/1422