Test – KMC Controls SAE-1152(OLD Style Board w/ LEDs) User Manual
Page 7

Test
A special test menu that can be used during setup is
available by temporarily shorting pins 1 and 2 on J4
on the Printed Circuir Board.
Short 1-2 on J4 to enter the test menu.
1. RELAY IS OFF
D9 and D10 flash continuously to indicate this
mode. If D13 is lit then the relay is ‘ON’.
Press
2. BUZZER IS OFF
D10 and D11 flash continuously to indicate this
mode. If D13 is lit then the buzzer is ‘ON’. The
buzzer hardware jumper must be set to “Buzzer
On” for the buzzer to operate.
Press
3. LED IS OFF
D11 and D12 flash three times to indicate this
mode. Then all LEDs are turned off.
Press
4. SENSOR (SS)
D12 and D13 flash continuously to indicate this
mode.
D9 is lit = range of 0-250 ppm
D10 is lit = range of 0-500 ppm
D9 & D10 are lit = range of 0-300 ppm.
This item is factory set to the correct sensor type
and should never be changed unless the sensor
type is replaced.
Press
5. OUTPUT 4mA or OUTPUT 0V
D9, D10 and D11 flash three times to indicate
this mode. The output is indicated on the LEDs.
This item will test the analog output, either
current or voltage depending on the jumper
position. Use the
select as applicable:
4 (D9)
8 (D10)
12 (D11)
16 (D12)
20 mA (D13)
0 (none)
1 (D9)
2 (D10)
3 (D11)
4 (D12)
5 VDC (D13)
Press
6. 0
0
This item is for factory use only.
0
0
Use the
menu.