Wiring, Modular to modular (hso-22xx cable), Modular to leads (hso-5012 cable) – KMC Controls CTE-5201-16 User Manual
Page 2: Modular to leads (hso-5012 cable) 2

CTE-5201
2
Installation and Operation Guide
Wiring
Modular to Modular (HSO-22xx Cable)
Use HSO-22xx cables to connect the ther-
mostat to MEP-4x42 actuators, using the
modular connectors, as shown in the chart
and sample application below.
HSO-5010 3-Way
“Y” Modular Connector
HSO-2121
Transformer Cable
CTE-5201-16 Analog Electronic Thermostat
Up to 6 MEP-4x42s
on each side
of the transformer
(with HSO-2212s)
HSO-2212
actuator cable,
12-foot length
between actuators
Wires: Orange
& Orange Stripe
T
Wires: Green
& Green Stripe
XEE-6xxx-xxx
Transformer
24 VAC (+20/–15),
4 VA Per Actuator
HSO-2250 Thermostat Cable, 50-foot (typical)
Cable P/N
Cable Length
HSO-2203
3 feet
HSO-2206
6 feet
HSO-2212
12 feet
HSO-2220
20 feet
HSO-2250
50 feet
Modular to Leads (HSO-5012 Cable)
If using the HSO-5012 cable, plug the modular con-
nector into the thermostat, and connect the stripped
leads as follows:
• Blue stripe to actuator signal input (proportional
2–10 VDC)
• Blue to power (14–19 VDC)
• Green and Green-Stripe (twisted together) to
common
• (Wires from Pins 1 and 6 are not connected)
3/8"
2"