CTE-5202 Electronic Room Thermostat with LCD Display

3

Installation and Operation Guide

NOTE: AO1 is typically used to control the cool-

ing output (primary air damper or cooling

valve), and AO2 is used to control the heat-

ing output (VAV reheat or heating valve).

2° F

2° F

2° F

AO2 Disabled

(12 Volts)

SEQUENCE # 1: SINGLE DUCT COOLING, FAN BOX (with REE-5002, REE-5017, or REE-5024)

COLD AIR SEQUENCE

12 Volts

AO2 (DA)

0-12 Volts

AO1 (DA)

Setpoint

AO1 MIN

HOT AIR SEQUENCE (Morning Warm Up)

AO1 (RA)

AO1 MAX

AO1 MAX

AO1 MIN

Temp. Increasing

6 Volts

Setpoint

2° F

Of Loop

10%

2° F

2° F

AO1 MIN

AO1 MAX

AO1 MAX

AO1 (RA)

HOT AIR SEQUENCE (Morning Warm Up)

AUX

AO1 MIN

COLD AIR SEQUENCE

AO1 (DA)

AO2 (RA)

0 Volts

12 Volts

SEQUENCE # 2: SINGLE DUCT COOLING WITH REHEAT AND AUXILIARY FLOW

AO2 Disabled

(0 Volts)

Temp. Increasing

Cooling

Setpoint

Heating

Setpoint

Heating

Setpoint

SEQUENCE # 3:

INDEPENDENT HEATING AND COOLING CONTROL

(Dual Duct VAV, Baseboard, Single Zone AHU)

AO2 MAX

AO2 MIN

AO2 (RA)

AO1 (DA)

AO1 MIN

AO1 MAX

Cooling

Setpoint

Heating

Setpoint

Temp.

Increasing

2° F

2° F

NOTE: For additional details of sequence op-

erations, see the

CTE-5202 Applications

Guide

.

The ADVANCE menu enables changing (via the

Up/Down buttons) the values of:
• DEAD BD—Deadband or “minimum setpoint

differential” (adjustable from 1 to 10° F, 2° F default)

• SETBACK—Standby/unoccupied setback offset

(adjustable from 0 to 10° F, 2° F default)—does not

apply to morning warmup

• PROP BD—Loop proportional band (adjustable

from 1 to 10° F, 2° F default)

• Rm OFST—Room temperature offset (adjustable

±5° F, 0 default)

• CNG OVR—changeover temperature (adjustable

from 55 to 85° F, 77° F default)

• I TIME—Loop integral time (adjustable from 0 to

60, 30 minutes default, 0 = cancel integral action)

The SYSTEM menu enables changing:
• Sequence (SEQ1, SEQ2, or SEQ3)—see

Sequences charts

• °F (ENGLISH) or °C (METRIC)
• BLANK—Display blanking (NO or YES)—

when blanked, the temperature will display for

no more than 30 seconds after a button is pushed

When done, navigate to (flashing) Exit to save

changes. Letting the menu time-out (about 30

seconds) will not permanently save changes.