beautypg.com

Operation, Change setpoint, Change configuration – KMC Controls CTE-5202W User Manual

Page 2

background image

CTE-5202 Electronic Room Thermostat with LCD Display

2

Installation and Operation Guide

Operation

Change Setpoint

To change the setpoint:
1. Push the Setpoint button (or either Up/Down

button) to display the current value.

NOTE: Sequences 2 and 3 have two setpoints

indicated by “snowflake/cool” and “fire/

heat” icons. When the Cooling setpoint is

showing, pushing the Setpoint button will

display the Heating setpoint.

2. Use the Up/Down buttons to change the value.
3. Press the Setpoint button again, and the thermo-

stat will control at the new setpoint. (Alternately,

after about 30 seconds of no activity, the display

reverts back to displaying room temperature.)

Change Configuration

Press and hold both the Up and Down arrows

buttons for about ten seconds until the display starts

flashing “LIMITS.”

NOTE: When a menu is flashing (LIMITS,

ADVANCE

, SYSTEM, or EXIT),

pressing Up or Down displays the next

menu item and pressing Setpoint selects

that menu. When a menu is NOT flashing

(e.g., DEAD BD), pressing Up or Down

changes the value and pressing Setpoint

displays the next menu item.

To change any of the limits (output span) when

“LIMITS” is flashing, press the Setpoint button

until the desired limit (AO1 MIN, AO1 MAX, AO1

AUX

, AO2 MIN, or AO2 MAX) is flashing on the

screen. (Limits are adjustable from 0 to 12 VDC, with

MIN = 0, MAX = 12, and AUX = 0 as defaults.

) Use the

Up and Down buttons to change the desired values.

(If no Auxiliary Flow is desired, set AO1 AUX to 0.)
To change any of the system or advanced features,

press the Up or Down button until the desired (flash-

ing) ADVANCE or SYSTEM menu appears and

then press the Setpoint button.

3. With the hex screws toward the floor, fasten the

backplate to the outlet/handy box with the sup-

plied screws. (The backplate mounts directly on

vertical 2 x 4 inch boxes, but requires an HMO-

1161/HMO-1161W wall plate for horizontal 2 x 4,

4 x 4, or other boxes.)

4. Connect the wires to the terminal block:

“Heating” output (REE-50xx reheat relay

modules and heating valves) to AO2 and

T

(Common)

“Cooling” output (VAV dampers and cooling

valves) to AO1 and

T

(Common)*

Changeover (temperature) sensor (Type III,

10K ohm thermistor) and/or standby/unoccu-

pied setback contact to AI1 and

T

(Common).

(See

External Input (AI1) on page 4

.)

24 VAC transformer’s neutral lead to

T

(Com-

mon) and phase lead to

~

. Alternately, 14–35

VDC can be used with + connected to

~

and

– connected to

T

(Common).

*NOTE: For additional wiring details, cross-

references sample applications, and

examples of AO1 being used for heating

instead of or in addition to cooling, see the

CTE-5202 Applications Guide

.

5. Place the top of the thermostat over the top of

the mounting base and swing it down over the

hex screw brackets. Be careful not to pinch the

wiring.

6. Back the hex screws out of the backplate brackets

(counterclockwise) until they engage the ther-

mostat and hold it in place.

NOTE: For examples of applications, including

replacing a CTE-510x with the CTE-5202,

see the

CSP-5001/5002 Applications Guide

.

~

T

T

AO2

“Heating” Output

AO1

“Cooling” Output

Common
Common
Power (AC Phase or DC +)

Input

AI1

(

Colder

Room Temperature

Warmer

)

Cooling

Setpoint

Heating

Setpoint

Proportional

Band

Proportional

Band

Deadband

(Cooling)

Setback

(Heating)

Setback

Max.
Limit

Min.

Limit

Output

Span

This manual is related to the following products: