7-16

GV3000/SE 230 VAC 1-20 HP Drive, Hardware Reference Version 6.04

Parameters/Wiring Connections

The following parameter must be set:

P.000: Control Source

Terminal 22 On = Reset

The following parameters must be set:

P.000: Control Source
P.025: Stop Type

Terminal 23 Off = Stop
Terminal 24 On Transition = Start

Used with older Snubber Resistor Braking Kits that require a gate
turn-on signal from the drive (for example, the M/N 2DB2010
series).

Note that terminals 26 and 27 are not to be used with Snubber
Resistor Braking Kits M/N 2SR20400, 2SR20600, 2SR21200,
2SR21800, 2SR20300, and 2SR20450.

Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

22

23

24

25

26

27

Description

Digital Input 3
(Reset)

Digital Input 2
(Stop)

Digital Input 1
(Start)

24 VDC Isolated Common

Snubber Resistor Braking
Control Signal

+24 VDC Isolated Common

Wiring the Reset Input

Wiring the Snubber Resistor

Wiring the Stop/Start Inputs

16

22

RESET

16

24

START

16

23

STOP