beautypg.com

3 rs-232 communication port, 4 option board connector, 5 operator interface module connector – Rockwell Automation GV3000/SE AC Drive 1-20HP, 230VAC Ver. 6.04 Hdwe Ref, Install, Troubleshooting User Manual

Page 25

background image

2-11

About the Drive

Figure 2.8 – Typical Terminal Strip Connections

2.4.3 RS-232 Communication Port

The Regulator board contains a 9-pin D-shell RS-232 communication port (J8). This
port provides RS-232 communication between the GV3000/SE drive and a personal
computer running the Control and Configuration (CS3000) software. See figure 2.5.
Refer to instruction manual D2-3348, for more information about the CS3000
software.

2.4.4 Option Board Connector

The flat-ribbon cable connector (J3) on the left side of the Regulator board is a
parallel bus connection port that provides a means of attaching optional boards
such as the DeviceNet Option board, the RMI board, the AutoMax Network Option
board, or similar boards to the GV3000/SE drive. See figure 2.5. The option board
is mounted below the Regulator board inside the drive. Refer to the appropriate board
instruction manual for more information. Refer to section 2.5 of this manual for
more information on optional drive kits.

2.4.5 Operator Interface Module Connector

The flat-ribbon connector J7 provides a means of attaching the optional Operator
Interface Module (OIM). The OIM is available for use as a remote keypad for the
GV3000/SE drive.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

17 18 19

21 22 23 24 25 26 27 28 29 30 31

16

20

TX

RX

REGULATOR COMMON

+15 VDC

PHASE A

PHASE A NOT

PHASE B

PHASE B NOT

REGULATOR COMMON

ANALOG METER OUTPUT

REGULATOR COMMON

ISOLATED REFERENCE VOLTAGE

VDC SPEED REFERENCE

mA SPEED REFERENCE

ISOLATED REFERENCE GND

+24 VDC

DIGITAL INPUT 8 (REMOTE/LOCAL)

DIGITAL INPUT 7 (RAMP 1/RAMP 2)

DIGITAL INPUT 6 (FORWARD/REVERSE)

FUNCTION LOSS

RUN/JOG

RESET

STOP

START

+24 VDC COMMON

SNUBBER RESISTOR BRAKING SIGNAL

+24 VDC COMMON

N.C. RELAY CONTACT

N.C. RELAY COMMON

N.O. RELAY CONTACT

N.O. RELAY COMMON

RS-232

CONNECTIONS

ENCODER

CONNECTIONS

ANALOG
OUTPUT

ANALOG

SPEED

REFERENCE

SNUBBER

BRAKING

STATUS
RELAYS

DIGITAL INPUTS

(ISOLATED 24 VDC)

CONFIGURABLE

Factory Installed