Rockwell Automation GV3000/SE AC Drive 1-20HP, 230VAC Ver. 6.04 Hdwe Ref, Install, Troubleshooting User Manual
Page 62
![background image](/manuals/581284/62/background.png)
7-12
GV3000/SE 230 VAC 1-20 HP Drive, Hardware Reference Version 6.04
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
16
17
Description
+24 VDC Power Supply
Digital Input 8
(Default - Remote/Local)
Parameters/Wiring Connections
Current limited for remote input logic use only.
Digital input 8 is control function programmable through
parameter P.007.
The following parameters must be set:
P.000: Control Source
(Only active when P.000 = rE)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or Preset
Speeds)
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following parameters
can affect digital input 8.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
Terminal 17 On = Local Control
Diagram shows factory setting.
Wiring a Remote/Local Input
ATTENTION: If a maintained start contact is used when the control source = rE, switching from local to
remote from the terminal strip will cause power to be applied to the motor if the remote start contact is
closed. Stay clear of rotating machinery in this case. Failure to observe this precaution could result in
bodily injury.
!
16
17
REMOTE
LOCAL