Rockwell Automation GV3000/SE AC Drive 1-20HP, 230VAC Ver. 6.04 Hdwe Ref, Install, Troubleshooting User Manual
Page 30

3-2
GV3000/SE 230 VAC 1-20 HP Drive, Hardware Reference Version 6.04
3.1.2 Determining Total Area Required Based on Drive Dimensions
Drive dimensions and weights are listed in table 3.2. Overall dimensions are
illustrated in figure 3.1 as an aid in calculating the total area required by the
GV3000/SE drives.
Table 3.2 – Drive Dimensions and Weights
Condition
Operating Temperature (Ambient)
Storage Temperature (Ambient)
Humidity
Specification
0
°
to 40
°
C (32
°
to 104
°
F)
–40
°
to +65
°
C (–40
°
to +149
°
F)
5 to 95% (non-condensing)
•
Be sure that drives are away from oil, coolants, or other airborne contaminants.
•
Do not install the drive above 1000 meters (3300 feet) without derating output
power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet), derate
the output current 1%.
•
Verify that the drive location will meet the environmental conditions specified in
table 3.1.
Table 3.1 – Ambient Conditions
GV3000/SE
Drive
1V21XX
1V24XX
2V21XX
2V24XX
3V21XX
3V24XX
5V21XX
5V24XX
7V21XX
7V22XX
10V21XX
10V22XX
15V21XX
15V22XX
20V21XX
20V22XX
Dim. A
222.3 mm
8.75"
280.7 mm
11.05"
288.0 mm
11.34"
Dim. B
280.7 mm
11.05"
338.3 mm
13.32"
463.0 mm
18.23"
Dim. C
198.1 mm
7.80"
247.9 mm
9.76"
223.0 mm
8.78"
Dim. D
254.3 mm
10.01"
309.1 mm
12.17"
442.0 mm
17.40"
Dim. E
199.9 mm
7.87"
199.9 mm
7.87"
238.0 mm
9.37"
Weight
6.4 kg
14 lbs
9.1 kg
20 lbs
15.9 kg