Wiring the Regulator Board Terminal Strip

Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

18

Description

Digital Input 7
(Default - Ramp 1/Ramp 2)

Parameters/Wiring Connections

Digital input 7 is control function programmable through
parameter P.007. The following parameters must be set:

P.000: Control Source
P.001: Accel Time 1 (Ramp 1)
P.002: Decel Time 1 (Ramp 1)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and

assigns a control function to digital inputs 6 to 8).

P.008: Terminal Strip Speed Reference Source (Analog, Motor

Operated Potentiometer (MOP), or Preset Speeds)

P.017: Accel Time 2 (Ramp 2)
P.018: Decel Time 2 (Ramp 2)

Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 7.

P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8

Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.

Terminal 18 On = Ramp 2
Diagram shows factory setting.

Wiring an Additional Ramp Input

16

18

RAMP 1

RAMP 2