beautypg.com

Rockwell Automation GV3000/SE AC Drive 1-20HP, 230VAC Ver. 6.04 Hdwe Ref, Install, Troubleshooting User Manual

Page 50

background image

6-2

GV3000/SE 230 VAC 1-20 HP Drive, Hardware Reference Version 6.04

ATTENTION: Do not route signal and control wiring with power wiring
in the same conduit. This can cause interference with drive operation.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if
a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled to eliminate the possible shock hazard
from cross-coupled motor leads. Failure to observe these precautions
could result in bodily injury.

Step 2. Connect the three-phase AC output power motor leads to terminals U/T1,

V/T2, W/T3 on the power terminal strip.

Step 3. Tighten the three-phase AC output power terminals to 1.2-1.4 Newton-

meters (10-12 lb-in) for 1-5 HP drives, 2.0-2.4 Newton-meters (17-20 lb-in)
for 7.5 and 10 HP drives, and 2.5-2.9 Newton-meters (22-26 lb-in) for 15
and 20 HP drives.

!