297 local owner – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 97

Parameter Descriptions
4-65
Adapter that has requested exclusive control of drive logic functions.
If an adapter is in local lockout, all other functions (except stop) on all other modules
are locked out and non-functional. Local control can be obtained only when the drive
is stopped.
Parameter number whose value will be written from a communications device data
table.
Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type will disable the link
Refer to the appropriate communications option board manual for datalink information.
Parameter number whose value will be written from a communications device data
table.
Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type will disable the link.
Refer to the appropriate communications option board manual for datalink information.
297
Local Owner
Range:
See Stop Owner (288)
Default:
Read Only
Access:
1
Path: Communication>Masks & Owners
See also:
276 - 285
300
301
Data In A1 - Link A Word 1
Data In A2 - Link A Word 2
Range:
0 to 387 [1]
Default:
0 (Disabled)
Access:
1
Path: Communication>Datalinks
See also:
302
303
Data In B1 - Link B Word 1
Data In B2 - Link B Word 2
Range:
0 to 387 [1]
Default:
0 (Disabled)
Access:
1
Path: Communication>Datalinks
See also: