146 s curve, 147 current lmt sel, 148 current lmt val – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 64

4-32
LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Sets the rate of deceleration for all speed decreases.
Max Speed / Decel Time = Decel Rate
Two decel times exist to enable deceleration rate changes “on the fly” using a building
automation system command, digital input, or F-Key on the LCD OIM, if configured
(see chapter 2).
Sets the percentage of acceleration or deceleration time that is applied to the ramp as
S Curve. Time is added; 1/2 at the beginning and 1/2 at the end of the ramp.
Selects the source for the adjustment of current limit (i.e., parameter, analog input,
etc.).
Defines the current limit value when Current Lmt Sel (147) = Cur Lim Val.
142
143
Decel Time 1
Decel Time 2
Range:
0.1 to 100.0 sec [0.1 sec]
Default:
10.0 sec
Access:
142=0
143=0
Path: Dynamic Control>Ramp Rates
See also:
142, 143, 146, 361-366
146
S Curve %
Range:
0 to 100% [1%]
Default:
0%
Access:
0
Path: Dynamic Control>Ramp Rates
See also: 140 - 143
147
Current Lmt Sel
Range:
0 = Curr Lim Val
1 = Analog In 1
2 = Analog In 2
Default:
0 = Cur Lim Val
Access:
0
Path: Dynamic Control>Load Limits
See also:
148, 149
148
Current Lmt Val
Range:
Based on Drive Type [0.1 Amps]
Default:
Based on Drive Type (approximately 150%)
Access:
0
Path: Dynamic Control>Load Limits
See also:
147, 149