343 analog out scale hi, 344 analog out scale lo – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 105

Parameter Descriptions
4-73
Sets the analog output value when the source value is at maximum.
Scaling the Analog Output
The user defines the scaling for the analog output by entering analog output voltages
into Analog Out1 Lo and Analog Out1 Hi. These two output voltages correspond to the
bottom and top of the possible range covered by the quantity being output. The output
voltage will vary linearly with the quantity being output. The analog output voltage will
not go outside the limits defined by Analog Out1 Lo and Analog Out 1 Hi. See
table 4.2.
Sets the analog output value when the source value is at minimum.
Refer to Analog Out Scale Hi (343) for more information.
343
Analog Out Scale Hi
Range:
0.0 to 20.0 mA / 0.0 to 10.0 V [0.1 mA / 0.1 V]
Default:
20.0 mA / 10.0 Volts
Access:
0
Path: Inputs & Outputs>Analog Outputs
See also:
342
Table 4.2 – Analog Output Scaling
Options
Analog Out1 Value Corresponds to:
Analog Out 1 Hi (343)
Value Corresponds
to:
Analog Out Absolut
(341) = Disabled
Analog Out Absolut
(341) = Enabled
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Output Freq
Commanded Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Output
%Motor OL
%Drive OL
Application
–[Maximum Freq]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
4.000
0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
4.000
+[Maximum Freq]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated
200% Rated
100%
100%
100%
100%
100%
100%\
20.000
344
Analog Out Scale Lo
Range:
0.0 to 20.0 mA / 0.0 to 10.0 V [0.1 mA / 0.1 V]
Default:
4.0 mA / 4.0 Volts
Access:
0
Path: Inputs & Outputs>Analog Outputs
See also: 342, 343