Table 5.6 – Fault Descriptions and Corrective Actions
Fault
No
.
Ty
p
e
Description
Action
Analog In
Loss
29
➀
➂
An analog input is configured
to fault on signal loss. A signal
loss has occurred.
Configure with Anlg In 1, 2
Loss (324, 327).
1.
Check parameters.
2.
Check for broken/loose
connections at inputs.
Anlg Cal
Chksum
108
➁
The checksum read from the
analog calibration data does
not match the checksum
calculated.
Replace drive.
Auto Rstrt
Tries
33
➂
Drive unsuccessfully
attempted to reset a fault and
resume running for the
programmed number of Auto
Rstrt Tries (174).
Enable/disable with Fault
Config 1 (238).
Correct the cause of the fault
and manually clear.
AutoTune
Aborted
80
The autotune procedure was
canceled by the user.
Restart procedure.
DB
Resistance
69
Resistance of the internal DB
resistor is out of range.
Replace resistor.
Decel Inhibit
24
➂
The drive is not following a
commanded deceleration
because it is attempting to
limit bus voltage.
1.
Verify input voltage is within
drive specified limits.
2.
Verify system ground
impedance follows proper
grounding techniques.
3.
Disable bus regulation
and/or add dynamic brake
resistor and/or extend
deceleration time.
Drive
OverLoad
64
Drive rating of 110% for 1
minute or 150% for 3 seconds
has been exceeded.
Reduce load or extend Accel
Time (140).
Excessive
Load
79
Motor did not come up to
speed in the allotted time.
1.
Uncouple load from motor.
2.
Repeat Autotune (61).
FluxAmpsRef
Rang
78
The value for flux amps
determined by the autotune
procedure exceeds the
programmed Motor NP FLA
(42).
1.
Reprogram Motor NP FLA
(42) with the correct motor
nameplate value.
2.