Using the Start-Up Routines on the LCD OIM
1-3
You do not have to configure all of the parameters in all 7 menus. The first menu
selection, Quickstart, contains the minimum basic parameters that must be configured
before running the drive. These parameters are listed in table 1.1.
If your application requires adjustment to parameters beyond those listed in table 1.1,
you can adjust the parameters in any or all of the next 6 selections in the Start-Up
menu, or you can adjust parameters individually through the Parameters menu (see
section 3.3).
As you adjust the parameters in the Start-Up routines, record them in Appendix C or
D.
When you have completed adjusting all of the parameters in the Start-Up routines that
your application requires, select the last item in the menu, Done.
Exiting Before Completing the Start-Up Routines
To exit the Start-Up routines, press the F4 key (Exit). When you select the Start-Up
icon from the main menu again, you will be prompted to either continue or restart the
Start-Up routines. If you select “continue,” you will be returned to the point at which
you exited.
Table 1.1 – Quickstart Parameters
Parameter
No.
Parameter Name
155
Stop Mode A
42
Motor NP FLA
81
Minimum Speed
82
Maximum Speed
140
Accel Time 1
142
Decel Time 1
90
Speed Ref A Sel
362
Digital In2 Sel