175 auto rstrt delay, 178 sleep mode enable, 179 sleep-wake ref – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 71: 180 wake level

Parameter Descriptions
4-39
•
Setting Auto Restrt Tries to zero.
•
Occurrence of a fault that is not auto-resettable.
•
Removing power from the drive.
•
Exhausting an auto-reset/run cycle.
Note that two autotuning status bits are provided in Drive Status 2 (210): an active
status bit and a countdown status bit.
Sets the time between restart attempts when the auto restart feature is enabled. Refer
to Auto Rstrt Tries (174) for more information about the auto restart feature.
Enables the Sleep-Wake function. This parameter is not used with LiquiFlo AC drives.
Selects the source of the input controlling the Sleep-Wake function. This parameter is
not used with LiquiFlo AC drives.
Defines the analog input level that will start the drive. This parameter is not used with
LiquiFlo AC drives.
175
Auto Rstrt Delay
Range:
0.5 to 30.0 sec [0.1 sec]
Default:
1.0 sec
Access:
0
Path: Dynamic Control>Restart Modes
See also:
174
178
Sleep Mode Enable
Range:
0 = Disabled
Default:
0 = Disabled
Access:
1
Path: Dynamic Control>Restart Modes
See also:
179
Sleep-Wake Ref
Range:
1 = Analog In 1
2 = Analog In 2
Default:
2 = Analog In 2
Access:
1
Path: Dynamic Control>Restart Modes
See also:
180
Wake Level
Range:
Sleep Level / 20.000 mA, 10.000 volts [0.001 mA, 0.001 V]
Default:
6.000 mA, 6.000 V
Access:
1
Path: Dynamic Control>Restart Modes
See also:
181