43 motor np hertz, 44 motor np rpm, 45 motor np power – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual
Page 42: 46 mtr np pwr units

4-10
LiquiFlo 1.5 AC Drive, Software Reference Version 1.2
Set to the motor nameplate rated frequency. The motor nameplate base frequency
defines the output frequency when operating at rated voltage, rated current, rated
speed, and rated temperature.
Set to the motor nameplate rated RPM. The motor nameplate RPM defines the rated
speed when operating at motor nameplate base frequency, rated current, base
voltage, and rated temperature. This is used to calculate slip.
Set to the motor nameplate rated power. The motor nameplate power is used with the
other nameplate values to calculate default values for motor parameters to assist the
commissioning process. This may be entered in horsepower or in kilowatts as
selected in parameter 46.
Set to the power units shown on the motor nameplate. This parameter determines the
units for parameter 45.
43
Motor NP Hertz
Range:
5.0 to 250.0 Hz [0.1 Hz]
Default:
Based on Drive Type
Access:
0
Path: Motor Control>Motor Data
See also:
44
Motor NP RPM
Range:
60 to 24000 RPM [1 RPM]
Default:
1750 RPM
Access:
0
Path: Motor Control>Motor Data
See also:
45
Motor NP Power
Range:
0.00 to 1000.00 [0.01 kW]
Default:
Based on Drive Type
Access:
0
Path: Motor Control>Motor Data
See also:
46
32
46
Mtr NP Pwr Units
Range:
0 = Horsepower
1 = kiloWatts
Default:
Based on Drive Type
Access:
0
Path: Motor Control>Motor Data
See also: