beautypg.com

272 drive ref rslt, 273 drive ramp rslt, 276 logic mask – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual

Page 92

background image

4-60

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Present frequency reference scaled as a DPI reference for peer-to-peer
communications. The value shown is the output prior to the accel/decel ramp and any
corrections supplied by slip comp, PI, etc.

Present frequency reference scaled as a DPI reference for peer-to-peer
communications. The value shown is the value after the accel/decel ramp but prior to
any corrections supplied by slip comp, PI, etc.

Disables manual requests at the port corresponding to bit number.

272

Drive Ref Rslt

Range:

0 to 32767 [1]

Default:

Read Only

Access:

1

Path: Communication>Comm Control

See also:

273

Drive Ramp Rslt

Range:

0 to 32767 [1]

Default:

Read Only

Access:

1

Path: Communication>Comm Control

See also:

276

Logic Mask

Range:

See figure 4.27

Default:

See figure 4.27

Access:

1

Path: Communication>Masks & Owners

See also:

288 - 297

Figure 4.27 – Logic Mask (276)

1

1

1

0

1

1

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Issuing Command
0 =No Command
x =Reserved

Bit #

Digital In

DPI P

or

t 1

DPI P

or

t 2

DPI P

or

t 3

DPI P

or

t 4

DPI P

or

t 5

Nibble 1

Nibble 2

Nibble 3

Nibble 4