RTC Control: Hours
Direction: output from application to controller
Type: boolean
Values:
TRUE = RTC program hours will be applied by RTC Write.
FALSE = RTC program hours will be ignored.
Default FALSE until an initial value is specified in the application.
Description:
Defines whether the value of the RTC program variable named Hours should be
applied to the real-time clock the next time the RTC control variable named RTC
Write is set to TRUE.
Note: The RTC program variable is only updated if the RTC control variable RTC
Read is set to TRUE and all other RTC Control variables are set to TRUE.
RTC Control: Minutes
Direction: output from application to controller
Type: boolean
Values:
TRUE = RTC program minutes will be applied by RTC Write.
FALSE = RTC program minutes will be ignored.
Default FALSE until an initial value is specified in the application.
Description:
Defines whether the value of the RTC program variable named Minutes should be
applied to the real-time clock the next time the RTC control variable named RTC
Write is set to TRUE.
Note: The RTC program variable is only updated if the RTC control variable RTC
Read is set to TRUE and all other RTC Control variables are set to TRUE.
RTC Control: Seconds
Direction: output from application to controller
Type: boolean
Values:
TRUE = RTC program seconds will be applied by RTC Write.
FALSE = RTC program seconds will be ignored.
Default FALSE until an initial value is specified in the application.