Parameters for cip producer and consumer varaibles – Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 175

Document: 553633
ICSTT-RM405f-EN-P
Issue 07
8-5
Parameters for CIP Producer and Consumer Varaibles
Each production variable and consumption variable for CIP over Ethernet/IP
communications has a set of parameters as detailed in the tables.
Note: A maximum of 128 producer and 128 consumer variables can be defined.
Table 18:
Parameters for Production Variables
Description
Value(s)
Default
Remarks
Maximum number
of connections
1 to 10
5
The maximum number of simultaneous
consumers of the particular variable (†)
Note: (†) The AADvance controller rejects any CIP requests to connect to a
produced variable beyond the maximum number of connections (255). Do not set the
number of connections higher than necessary because each connection uses resources
from a limited pool.
Table 19:
Parameters for Consumption Variables
Description
Value(s)
Default
Remarks
Producer
A unique string
Can include spaces and
other punctuation
characters
None
A user-defined name for the producing device
labelled 'Device Name' in Producer List.
Path to Producer
A valid address for a
Logix controller
None
Labelled 'CIP Path to Device' in Producer List.
(refer to Configure an AADvance Variable as a
consumer)
Remote Tag Name A string
None
Specifies the name of the variable as it is known
to the Logix controller.
RPI (ms)
2 to 1,000
20 (‡)
Requested packet interval
Defines how frequently the Logix controller
should offer the variable to the AADvance
controller.
Note: (‡) The RPI should not be set below 200ms at the current release.