Discover Communications Fault-Finding

This procedure describes how to activate communications using the Discover tool.
After completing the steps, refresh the Discover tool's list of modules to test for

communications.
1) Ensure that the Ethernet cable is plugged into a socket above a fitted AADvance

controller – communications will not ‘pass through’ unused slots.

2) Ensure that the controller is activated by turning the locking bar. Wait for the

Ready LED to go green before refreshing the Discover tool. (The communications

tasks are not active until it is 'Ready').

3) Do not use an office network. Use an isolated hub or switch between the

computer and AADvance controller. Check that the hub/switch has LEDs lit for

the ports to both computer and controller, showing that the ports are working.

4) Open the Network Connections window. Open the Properties of the computer’s

network adapter (as used for configuring AADvance). Un-tick all protocol "items"

which are not immediately necessary, especially "Check Point SecuRemote" and
"iPass Protocol" (if present). You will need to leave "Internet Protocol" (or) "IPv4"

and "IPv6", "Client for Microsoft Networks", "File and Printer Sharing" and

"Network Monitor Driver" (if present) for normal Windows operation.

5) Disable the Windows Firewall, or any third-party firewalls and shields.
6) If you are using a laptop, disable Wireless. If you have more than one network

connection, disable the one you are not using. The Discover tool installed with

AADvance Workbench release 1.2 (1.20.109) will not discover with more than
one network connection available.

Configure the Controller Resource Number

When you build a new AADvance controller, or install a new 9100 processor base

unit, you have to configure the resource number stored in the controller. This is a kind

of device address, and it must also be configured in the application.
The procedure to configure the resource number uses the AADvanceDiscover

utility. To set the resource number do the following:
1) Make a note of the controller's MAC address (Controller ID); this is shown on

a label on the processor base unit. Install at least one 9110 processor module into
the processor base unit.

2) Make sure the program enable key is inserted in the KEY connector on the

processor base unit.

3) Start the AADvDiscover tool from the Start menu:

Start

All Programs

AADvance

AADvance Discover.