Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 152
5-54
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
1) Select the slot with the analogue output module.
The module status variable name
Variable field.
2) Select the channel to configure and click the Advanced tab.
The 9481/9482 Advanced Channel Settings dialog box opens.
3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Choose the advanced channel settings from the options.
Analogue Output Advanced Channel Settings
Each output channel from the 9481/9482 analogue output module supports the set of
control parameters detailed in the table.
Table 17:
Analogue Output Control Parameters
Description
Value(s)
Default
Remarks
Shutdown State
Off, Hold Last State,
Custom
Off
'Off' de-energizes the output during
a shutdown
'Hold Last State' forces the output
to remain in its last commanded
current, during a shutdown
'Custom' forces the output to go to
the value set in 'Custom Shutdown
Value', during a shutdown
Custom Shutdown
Value
As scaled range of
command value CV
-25
Output set when 'Shutdown State'
is set to 'Custom', during a
shutdown
Fail-Safe Guard
Band
0-100% of full scale
20mA (1% = 0.2mA)
1%
Threshold for discrepancy alarm
between command value CV and
Count CNT. A discrepancy alarm is
reported on parameter DIS.