1) Select the slot with the analogue output module.

The module status variable name that you assigned appears in the
Variable field.

2) Select the channel to configure and click the Advanced tab.

The 9481/9482 Advanced Channel Settings dialog box opens.

3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Choose the advanced channel settings from the options.

Analogue Output Advanced Channel Settings

Each output channel from the 9481/9482 analogue output module supports the set of
control parameters detailed in the table.

Table 17:

Analogue Output Control Parameters

Description

Value(s)

Default

Remarks

Shutdown State

Off, Hold Last State,

Custom

Off

'Off' de-energizes the output during

a shutdown

'Hold Last State' forces the output
to remain in its last commanded
current, during a shutdown

'Custom' forces the output to go to

the value set in 'Custom Shutdown
Value', during a shutdown

Custom Shutdown
Value

As scaled range of
command value CV

-25

Output set when 'Shutdown State'
is set to 'Custom', during a

shutdown

Fail-Safe Guard
Band

0-100% of full scale
20mA (1% = 0.2mA)

1%

Threshold for discrepancy alarm
between command value CV and

Count CNT. A discrepancy alarm is
reported on parameter DIS.