Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 84
![background image](/manuals/580880/84/background.png)
4-44
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module A 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module B 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module C 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.