Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 95
![background image](/manuals/580880/95/background.png)
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
4-55
RTC Control: Month
Direction: output from application to controller
Type: boolean
Values:
TRUE = RTC program month will be applied by RTC Write.
FALSE = RTC program month will be ignored.
Default FALSE until an initial value is specified in the application.
Description:
Defines whether the value of the RTC program variable named Month should be
applied to the real-time clock the next time the RTC control variable named RTC
Write is set to TRUE.
Note: The RTC program variable is only updated if the RTC control variable RTC
Read is set to TRUE and all other RTC variables are set to TRUE.
RTC Control: Day of Month
Direction: output from application to controller
Type: boolean
Values:
TRUE = RTC program day of month will be applied by RTC Write.
FALSE = RTC program day of month will be ignored.
Default FALSE until an initial value is specified in the application.
Description:
Defines whether the value of the RTC program variable named Day of Month should
be applied to the real-time clock the next time the RTC control variable named RTC
Write is set to TRUE.
Note: The RTC program variable is only updated if the RTC control variable RTC
Read is set to TRUE and all other RTC Control variables are set to TRUE.