Configuration Guide (AADvance Controller)
SNCP_KVB_ERR_NO_PRODUCER
0x04
At the beginning of a connection or
following "BindRespTimeout" milliseconds
during data exchange.
SNCP_KVB_ERR_BAD_CRC
0x05
Producer and consumer binding tables
CRC mismatch during connection
SNCP_KVB_ERR_IMPOSSIBLE_TO_
BIND
0x06
Conversion of structures not supported on
hetrogeneous binding link
SNCP_KVB_ERR_IP_DENIED
0X07 Producer only error, indicates that a
consumer with an unknown/unexpected IP
Address is requesting a bindings link. The
link is denied.
SNCP_KVB_ERR_BAD_PRODUCER_
ID
0X08 Producer only error, indicates that the
producer has received a bindings link
request from a consumer and that request
does not contain the expected producer
identity. The link is denied.
SNCP_KVB_ERR_BAD_GROUP_ID
0X09 Producer only error, indicates that the
producer has received a bindings link
request from a consumer, and that request
does not contain a known bound variable
group identity. The link is denied.
SNCP_KVB_ERR_BAD_BUFF_SIZE
0X0A Producer only error, indicates that either
the producer or consumer does not have
sufficient buffer space to translate the
bound variables so that the link cannot be
established.
SNCP_ERR_BAD_CONFIG
0X0B Producer only error, indicates that the
producer is unable to obtain the consumers
IP address information from the network
configuration file. The link is denied.