Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 86

4-46
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
FALSE = The voltage of the back-up battery is low or the battery is missing.
Description:
Reports the health status of the back-up battery in a processor module.
Note: The battery voltage is checked at start up, then re-checked every 24 hours
(elapsed time).
Processor Module B NVRAM Battery Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = The back-up battery in the 9110 processor module in the given slot is
present and its voltage is within acceptable limits.
FALSE = The voltage of the back-up battery is low or the battery is missing.
Description:
Reports the health status of the back-up battery in a processor module.
Note: The battery voltage is checked at start up, then re-checked every 24 hours
(elapsed time).
Processor Module C NVRAM Battery Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = The back-up battery in the 9110 processor module in the given slot is
present and its voltage is within acceptable limits.
FALSE = The voltage of the back-up battery is low or the battery is missing.
Description:
Reports the health status of the back-up battery in a processor module.
Note: The battery voltage is checked at start up, then re-checked every 24 hours
(elapsed time).